Xantrex Technology XW Portable Generator User Manual


 
Specifications
A–2 975-0307-01-01
Electrical Specifications
*Limited to Class 2 levels (100 VA) as in Chapter 2, page 2–5.
Nominal input network voltage 15 Vdc
Maximum operating current 200 mA @ nominal
input network voltage
Relay contact voltage rating 12 Vdc, 30 Vdc max.*
Maximum relay contact current 5 A DC*
Nominal 12/24 V thermostat input voltage 12 Vdc/24 Vdc* = On
Minimum 12/24 V thermostat input voltage 9.5 Vdc*
Maximum 12/24 V thermostat input voltage 30 Vdc*
Typical 12/24 V thermostat input current 14.6 mA @ 12 V
Nominal 12/24 V generator running B+ voltage 12 Vdc/24 Vdc*= On
Minimum 12/24 V generator running B+ voltage 9.5 Vdc*
Maximum 12/24 V generator running B+ voltage 30 Vdc*
Typical 12/24 V generator running B+ current 14.6 mA @ 12 V
Communication physical layer 2, CAN
Communication protocol Xanbus
Maximum cable length 130 ft. (40 m)