Xantrex Technology XW Portable Generator User Manual


 
Installation
2–14 975-0307-01-01
Type 6
Type 6 is a three-wire GlowStop configuration that has a normally closed
Run/Stop contact. This generator type is intended for Yamaha generators.
Figure 2-8
Type 6 Connection Diagram
For additional information, see
“Circuit Limitations” on page 2–5.
XW AGS Harness Wires Generator Wires
18
17
16
15
13
12
14
Relay 2
Relay 1
5A fuse
5A fuse
5A fuse
GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
PREHEAT
STOP
START
Table 2-9
Type 6 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
GlowStop
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
10 s
Preheat to crank delay
1 s
Crank time
15 s
Crank retry time
30 s
Gen Cool Down
30 s
Shutdown bypass time
0 s
Start tries
3