Xantrex Technology XW Portable Generator User Manual


 
The XW Auto Gen Start Menu
975-0307-01-01 3–9
QT End
Full name Quiet Time End
Purpose “QT End” is a changeable setting that defines the end of quiet time.
This setting also requires a setting for “QT Begin”.
Dependencies “QT End” functions only if the XW Auto Generator Start is in Automatic
mode. This setting requires “QT En” be set to [Enabled] and also requires
a setting for the “QT Begin” trigger. This setting is triggered by the
setting on the system clock, so ensure the clock on the XW System
Control Panel is set to the correct local time.
Gen Type
Full name Generator Type
Purpose “Gen Type” is a changeable setting for selecting the starting requirements
of the generator. The starting requirements determine how the XW Auto
Generator Start must be wired to the generator’s starting system. For more
information, see “Connecting the Generator” on page 2–8 or Appendix B.
Value Description
12:00AM to 11:59PM
(12-hour clock)
00:00 to 23:59
(24-hour clock)
At the time set for
“QT End” the XW Auto
Generator Start will be able to automatically start the
generator again. If a start trigger has occurred during
quiet time and is still active, the generator will start
immediately after quiet time ends.
Important:
“Gen Type” can only be changed after the system is put into
Standby. See “Putting the XW Auto Generator Start in Standby Mode” on
page 4–6.
Table 3-1
Generator Type Descriptions and Examples
Option
Description
Mode
For Technical
Details, see...
a
Examples of Generators
b
Type 1 GlowStop page 2–9 Generac
Type 2 GlowStop with no preheat page 2–10 Onan Diesel (Default)
Type 3 GlowStop with shutdown bypass page 2–11 Generac
Type 4 StartStop with Relay 3 prime page 2–12 Guardian/Generac Gas
Type 5 StartStop with Relay 3 preheat page 2–13 Guardian/Generac Diesel