Xantrex Technology XW Portable Generator User Manual


 
Installing the XW Automatic Generator Start
975-0307-01-01 2–11
Type 3
Type 3 is a three-wire GlowStop with shutdown bypass configuration.
The configuration shown in Figure 2-5 uses a shutdown bypass output to
temporarily disable the generator’s low oil pressure shutdown
functionality during cranking. Generators with this functionality often
have a manual means of disabling it during cranking.
Figure 2-5
Type 3 Connection Diagram
Table 2-6
Type 3 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
GlowStop/Shutdown bypass
Relay 3 mode
Preheat/Shutdown bypass
Gen Run signal hold time
0.5 s
Preheat time
20 s
Preheat to crank delay
0 s
Crank time
15 s
Crank retry time
30 s
Gen Cool Down
30 s
Shutdown bypass time
10 s
Start tries
3
For additional information, see
“Circuit Limitations” on page 2–5.
XW AGS Harness Wires Generator Wires
14
13
12
18
17
16
Relay 1
Relay 2
5A fuse
5A fuse
GENERATOR RUN SIGNAL
START
PREHEAT
STOP
BYPASS SHUTDOWN
GENERATOR BATTERY NEGATIVE (–)