Subaru RGD3300H Portable Generator User Manual


 
9
ENGLISHFRANÇAISEESPAÑOL
Recoil starter can be utilized for emergency
starting purpose. Before recoil starter operation,
please read the "(c) Emergency start"
(d) Starting with recoil starter
[down to - 6 °C] (See Fig.
33
-
!!11
,
!!22
)
Pull the starting cable out by the handle until
you feel a slight resistance. (See Fig. 3-!1)
Let the cable run back; in this way the entire
length of the starting cable can be used to start
the engine.
Devices which are not securely fastened should
be restrained with the foot.
Grip the handle with both hands.
Commence pulling the starting cable vigorously
and at an increasing speed (do not jerk it
violently) until the engine starts.
(See Fig. 3-!2)
If after several attempts of starting the
exhaust begins to emit white smoke,
move the speed adjustment lever to the
STOP position and pull the starting cable
out slowly 5 times.
Repeat the "(a) Before starting"
CAUTION
Follow the starting procedures described
below, without fail.
In case the starting cable is pulled in
short length, engine does not start due
to no cranking; the piston does not
reached to the TDC.
In case of poor pulling force at low
speed, engine does not start due to no
activation of centrifugal decompression
mechanism.
CAUTION
After this, the engine can only be
stopped with the starting key in the
emergency operating mode if the
emergency starting lever is first turned
back clockwise to the stop position.
WARNING
(c) Emergency start (See Fig.
33
-
!!00
)
If the shut-off valve is blocking the fuel supply as
a result of an electrical fault and the engine
therefore cannot be started, an emergency start
can be attempted.
Proceed as follows for this:
For emergency starting, turn the lever at fuel
shut-off solenoid q anti-clockwise by at least
90º using suitable pliers. The lead seal wire will
break off.
As soon as the emergency start lever is in the
starting position, the electric starter or recoil
starter can be used; (See Fig. 3-!0).
The oil level must always be checked before an
emergency start, as insufficient oil pressure can
lead to complete damage of the engine within a
very short time.
Immediately after a period of emergency running,
ascertain the cause of the fault and have it
rectified; page 21
" TROUBLESHOOTING".
Have the emergency-starting lever sealed once
again by a ROBIN service point.
When the automatic electrical shutdown system is
used, the emergency start described above means
that liability for risks must be accepted by the
operator (Engine manufacture assumes no
liability).
In case of difficulty contact the nearest ROBIN
service point.