(2) ALTERNATOR
Measure insulation resistance between each
terminal (Black or White) of 6-P connector from the
stator and the stator core.
If there is a wire which has insulation resistance less
than 1 M , replace the stator. Insulation failure
cause electrical leak which may result in
electrocution.
(3) CONTROL PANEL
With AC breaker turned ON, measure insulation
resistance between each portion of electrical parts
and earth (grounding) terminal or control panel itself.
Measure with the AC breaker on.
If there is a spot where insulation resistance less
than 1 M , replace the part.
Insulation failure may result in electrification, or an
electrical leak.