Subaru Robin Power Products RGV6100 Portable Generator User Manual


 
-
69
-
2-4 NO DC OUTPUT
2-4-1 CHECK THE AC OUTPUT.
Check the generator by following Step 2-1-1 through Step 2-1-3.
2-4-2 CHECK THE DC BREAKER.
If the DC breaker turned off while charging a bat-
tery, check the cables for short-circuit or connec-
tion in reverse polarity before resetting it on.
NOTE : If the DC output is used to charge a large
capacity battery or an over-discharged
battery, an excessive current may flow
causing.
2-4-3 CHECK THE DC FUSE.
Check the fuse in the fuse holder.
If the fuse is blown, check for the cause of fuse
blowing, and then replace with a new one.
FUSE : 10 A
NOTE : If the DC output is used to charge a large
capacity battery or an over-discharged
battery, an excessive current may flow
causing fuse blow.
2-4-4 CHECK THE WIRING.
Check all the wires to be connected correctly.
2-4-5 CHECK THE DIODE RECTIFIER.
Remove the control panel and check the diode
rectifier with a circuit tester.
Fig. 2-10
Fig. 2-12
Fig. 2-11
FUSE