CAT Titan 250 Portable Generator User Manual


 
Turbomachinery Package Specification Titan 250 Generator Set
12.1.2 Insect Screens
Optional insect screens can be installed on each side of the air inlet filters (except for
self-cleaning filters). This option is used with the air filter when large numbers of insects
are present. The insect screen design reduces the velocity of the air stream sufficiently to
allow most insects to fly away. Use of the screen helps to avoid clogging and premature
filter replacement. During cold weather operation, the insect screens should be removed
and stored due to a potential for ice or snow to clog the screens.
12.1.3 Self-Cleaning Barrier Type Air Filter (Updraft Type)
The self-cleaning barrier type air filter system is suitable for extreme environments where
dust loading or cold-weather operation is a concern. This system requires a suitable
supply of cleaning air. Cleaning air can be provided by the customer or supplied using
turbine compressor discharge pressure (Pcd) bleed air. If bleed air is used, an air heat
exchanger is provided for mounting in the air inlet ducting between the air inlet filter and
the turbine air inlet. Access to change filter elements from below must be provided
Standard features include:
Support leg kit
Dual differential pressure alarm and shutdown switch
Filter elements
Differential pressure gauge
Electrical connections prewired to a common junction box
12.1.4 Marine-Type
The marine-type air filter system is suitable for use in coastal, offshore, and tropical
locations. This system provides high efficiency removal of salt, water, and particulates.
This system consists of:
First stage marine vane separator/moisture eliminator
Second stage prefilter
Third stage high efficiency bag filters
Fourth stage marine vane separator/moisture eliminator
Access doors are provided in the first stage marine vane separator/moisture eliminator
for filter removal. Standard features include:
High performance drainage system
Transition outlet flange
Lifting lugs
Instrumentation panel
Differential pressure gauge
Electrical connections prewired to a common junction box
High differential pressure alarm and shutdown switches
12.1.5 Air Inlet Silencer
Optional air inlet silencers can be incorporated into the air inlet ducting to reduce noise
levels. Typical installations include one air inlet silencer..
12.1.6 Air Inlet Ducting and Support
An optional support structure and ducting can be provided for offskid support of the air
inlet filter and silencer assembly. Attaching hardware and a tube of sealant are provided
for one flange per duct.
© 2008 Solar Turbines Incorporated. All rights reserved. TPS250GS/908 - Preliminary