Athena Technologies 16C Weather Radio User Manual


 
38
39
Alarm Delay - the time delay between the detection of the alarm condi-
tion and the initiation and indication of the output action.
Alarm Inhibit - prevents low setpoint alarm activation during cold startup
applications.
Bias - allows the operator to compensate for any difference between sensor
temperature and the point to be measured. The process display and set-
point will be offset by the value entered in the Bias parameter in the input
menu. Ex: Desired temperature is 150 degrees. Sensor is adjacent to heater
and reads 50 degrees higher than the actual process temperature. Enter
bias of -50. Enter setpoint of 150. Process will display 150 even though
sensor will be measuring 200 degrees.
Blanking - controls the time the setpoint value display remains on. After the
set time, the setpoint value display turns off. Pressing any button causes the
setpoint value display to reappear for the selected time interval.
Cycle Time - The period of time in which the controller’s output completes
an on-off cycle (Proportional Output Type only).
Example: Output type = Mechanical relay
Cycle time = 10 seconds
Output power = 50%
Controller output = 5 seconds closed,
5 seconds open
Deadband - In On/Off temperature control, it is the band above or below
the setpoint where there is no output action. It has the effect of moving the
apparent setpoint.
Derivative (rate) - Adjusts the controller gain quickly in response to load
changes.
Failsafe State - designates the percentage of power output that the con-
troller defaults to after it detects a loop break condition and after the loop
break time has elapsed.
Filter (in Display menu) - changes the filtering speed for the process value
display only. It does not affect control. This parameter is mainly used to
slow down the flickering of the display when the decimal position chosen is
greater than zero.
Filtering (in Input menu) - sets the time period over which the process
value is averaged.
Highest Reading - records the highest process value read by the controller.
It may be reset to zero by using the Raise or Lower arrow keys.
Hysteresis - In On/Off temperature control, hysteresis represents the band
where the output changes state from deactivated to activated. It prevents
chattering around the setpoint and prevents rapid output cycling.
Integral (automatic reset) - slowly adjusts the position of the Proportional
Band (range of power output) to eliminate offset error.
Loop Break - a condition where the input is not changing or responding
properly to the output action. This could be caused by a thermocouple or
Glossary