17
Input Type JMPØ1 JMPØ2
Thermocouple Out Out
RTD Out Out
Voltage <100 mV Out Out
Voltage >100 mV In Out
Current Process In In
16
Input Menu
JMPØ1
JMPØ2
Input Menu (continued)
Display Parameter Selection
Input Type 100 ohm
compressed RTD
0-20 mA
4-20 mA
0-10 mV
0-50 mV
0-100 mV
10-50 mV
0-1 V
0-5 V
0-10 V
1-5 V
Input Jumper Settings
Note: When you ordered your controller, an input type was specified and the controller was set up
accordingly and calibrated for that input type at the factory. If you decide to change input type from
thermocouple to RTD or vice-versa, you will need to recalibrate the controller unless you ordered the
“Calibrate All” option. (Refer to page 56 for information on recalibration.) If you are changing from a
temperature input type to a linear input type, you MUST recalibrate and change the jumper settings as
indicated in the above table.
Temperature Input Type
Display Parameter Selection
Bias (Display offset) -100 to 100
Lower Setpoint Limit Span of Sensor
Upper Setpoint Limit Span of Sensor
Filtering 0.1-10.0 sec.
Linear Input Type
Display Parameter Selection
Bias (Display offset) -100 to 100
Low Scale -1999 to 9999
High Scale -1999 to 9999
Lower Setpoint Limit Span of Sensor
Upper Setpoint Limit Span of Sensor
Filtering 0.1-10.0 sec.
Input Menu