Multiquip DCA85usJ2 Portable Generator User Manual


 
PAGE 52 — DCA85USJ2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/22/11)
GENERATOR START-UP PROCEDURE (MANUAL MODE)
12. The tachometer gauge (Figure 51) will indicate the
speed of the engine when the generator is operating.
Under normal operating conditions this speed is
approximately 1800 RPM’s.
Figure 51. Engine Tachometer Gauge
13. Place the main, GFCI, and aux. circuit breakers in the
ON position (Figure 52).
Figure 52. Main, Aux. and GFCI
Circuit Breakers (ON)
14. Observe the generator’s ammeter (Figure 53) and
verify it reads the anticipated amount of current with
respect to the load. The ammeter will only display a
current reading if a load is in use.
Figure 53. Ammeter (Load)
15. The generator will run until manually stopped or an
abnormal condition occurs.
WARNING
NEVER stop the engine suddenly except in an
emergency.
STARTING (AUTO MODE)
When starting generator in AUTO mode use the “Manual
Start-up” procedure except where noted (see below).
CAUTION
When connecting the generator to a isolation (transfer)
switch, ALWAYS have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
NOTICE
When the generator is set in the AUTO mode, the
generator will automatically start in the event of
commercial power falling below a prescribed level
by means of a contact closure that is generated
automatically by a transfer switch.
WARNING
When running the generator in the AUTO mode,
remember the generator can start up at any time without
warning. NEVER attempt to perform any maintenance
when the generator is in the auto mode.
CAUTION
The engine speed switch must be set to the “High”
position when running in the auto-start mode. Failing
to set the switch in the proper position can result in
damage to your generator when it turns on.
NOTICE
When the MPEC control switch is placed in the AUTO
position, the engine glow plugs will be warmed and the
engine will start automatically.
DANGER
Before connecting this generator to any
building’s electrical system, a licensed
electrician must install an isolation
(transfer) switch. Serious damage to
the building’s electrical system may occur
without this transfer switch.