GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 14). To obtain some of
the voltages as listed in Table 7 (see below) will require a
ne adjustment using the voltage regulator (VR) control
knob located on the control panel.
Voltage Selector Switch
The voltage selector switch (Figure 14) is located above
the output terminal panel’s Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Figure 14. Voltage Change-Over Board
Voltage Selector Switch Locking Button
To lock the voltage selector switch, press and hold the
red button located at the bottom of the switch. While
holding the red button down, insert a pad lock into the hole
next to the button to retain it in the inward locked position.
When the lock is removed, the red button is spring loaded
and will return to its normal outward unlocked position
switch.
CAUTION
NEVER change the position of the voltage selector
switch while the engine is running. ALWAYS place
circuit breaker in the OFF position before selecting
voltage.
Table 7. Voltages Available
UVWO Output
Terminal Lugs
Voltage Selector Switch
3-Phase 240/139V Position
Voltage Selector Switch
3-Phase 480/270V Position
Line-Line
208V 220V 240V 416V 440V 480V
Line-Neutral 120V 127V 139V 240V 254V 277V
Voltage Selector Switch Single-Phase 240/120V Position
Line-Neutral/
Line-Line
120V
Line-Neutral
N/A N/A
240V
Line-Line
N/A N/A
Generator Amperage
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed..
GFCI Receptacle Load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the 2 twist lock auxiliary receptacles.
Tables 9 and 10 show what amount of current is available
at the GFCI receptacles when the output terminals and
twist lock receptacles are in use. Be careful that your load
does not to exceed the available current capability at the
receptacles.
Table 8. Generator Maximum Amps
Rated Voltage Maximum Amps
Voltage Selector Switch
1Ø 240/120 position (120V)
188.9 Amps (4 wire)
250 Amps x 2 (Zigzag)
Voltage Selector Switch
1Ø 240/120 position (240V)
94.4 Amps (4 wire)
250A (Zigzag)
Voltage Selector Switch
3Ø 240/139 position (240V)
204 Amps
Voltage Selector Switch
3Ø 480/277 position (480V)
102 Amps
Table 9. 1Ø GFCI Receptacle Load Capacity
KW in Use
Twist Lock (C6369)
Available Load
Current (Amps)
1Ø 240/120V
GFCI Duplex
5-20R 120V
60.0 0 amps/receptacle
58.8 5 amps/receptacle
57.6 10 amps/receptacle
56.4 15 amps/receptacle
55.2 20 amps/receptacle
Table 10. 3Ø GFCI Receptacle Load Capacity
KVA in Use
(UVWO Terminals)
Available Load
Current (Amps)
3Ø 240/480V
GFCI Duplex
5-20R 120V
85
0 amps/receptacle
80.8
5 amps/receptacle
76.7
10 amps/receptacle
72.5
15 amps/receptacle
68.4
20 amps/receptacle