Multiquip DCA85usJ2 Portable Generator User Manual


 
DCA85USJ2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/22/11) — PAGE 37
ENGINE OPERATING PANEL
10. Warning Lamp – This lamp will illuminate when a
critical engine fault has occured.
11. Pre-Heat Lamp – As the engine cranks, this lamp
will illuminate to indicate automatic preheating of the
engine. When the lamp turns off, the engine has been
preheated and will start automatically.
12. Emergency Stop Lamp – This lamp will illuminate
when the emergency stop button has been pressed
or a critical engine fault has occured.
13. Fuel Leak Detected Alarm Lamp – This lamp will
illuminate when a leak in the fuel tank containment
enclosure is detected.
14.
. Auto START/STOP Engine Controller (ECU) — This
controller has a vertical row of
status LED's (inset), that when lit,
indicate that an engine malfunction
(fault) has been detected. When a
fault has been detected the engine
controller will evaluate the fault
and all major faults will shutdown
the generator. During cranking
cycle, the ECU will attempt to
crank the engine for 10 seconds
before disengaging.
If the engine does not engage (start) by the third
attempt, the engine will be shutdown by the engine
controller’s Over Crank Protection mode. If the engine
engages at a speed (RPM's) that is not safe, the
controller will shutdown the engine by initializing the
Over Speed Protection mode.
Also the engine controller will shut down the engine in
the event of low oil pressure, high coolant temperature,
low coolant level, and loss of magnetic pickup.
These conditions can be observed by monitoring the
LED status indicators on the front of the controller
module.
A. MPEC Control Switch — This switch controls the
running of the unit. If this switch is set to the OFF/
RESET position, the unit will not run. When this switch
is set to the manual position, the generator will start
immediately.
If the generator is to be connected to a building’s
AC power source via an automatic transfer switch
(isolation), place the switch in the AUTO position. In this
position, should an outage occur, the automatic transfer
switch (ATS) will start the generator automatically
via the generator’s auto-start contacts connected to
the ATS’s start contacts. Please refer to your ATS
installation manual for further instructions for the
correct installation of the auto-start contacts of the
generator to the ATS.
B. Low Oil Pressure — Indicates the engine pressure
has fallen below 15 psi (103 kPa). The oil pressure
is detected using variable resistive values from the
oil pressure sending unit. This is considered a major
fault.
C. High Coolant Temperature — Indicates the engine
temperature has exceeded 239°F (110°C). The engine
temperature is detected using variable resistive values
from the temperature sending unit. This is considered
a major fault.
D. Overcrank Shutdown — Indicates the unit has
attempted to start a pre- programmed number of
times, and has failed to start. The number of cycles
and duration are programmable. It is pre-set at 3
cycles with a 10 second duration. This is considered
a major fault.
E. Overspeed Shutdown — Indicates the engine is
running at an unsafe speed. This is considered a
major fault.
F. Engine Running — Indicates that engine is running
at a safe operating speed.