DCA70SSJU4i
GENERATOR OUTPUTS
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 15). To obtain some of
the voltages as listed in Table 9 (see below) will require a
fine adjustment using the voltage regulator (VR) control
knob located on the control panel.
The voltage selector switch (Figure 15) is located above
the output terminal panel’s Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection..
Figure 15. Voltage Selector Switch
change the position of the voltage selector
switch while the engine is running. place
circuit breaker in the OFF position before selecting
voltage
3Ø
208V 220V 240V 416V 440V 480V
1Ø 120V 127V 139V 240V 254V 277V
1Ø
120V
Line-Neutral
N/A N/A
240V
Line-Line
N/A N/A
Table 10 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the three twist lock auxiliary receptacles.
Figure 18 and Table 12 show what amount of current is
available at the GFCI receptacles when the output terminals
and twist lock receptacles are in use. Be careful that your
load does not to exceed the available current capability at
the receptacles.
1Ø 120 Volt
155.5 X 2 amps (4 wire)
168 amps X 2 (Zigzag)
1Ø 240 Volt
78.8 amps (4 wire)
168 amps (Zigzag)
3Ø 240 Volt 168 amps
3Ø 480 Volt 84 amps
KW in Use
1Ø 240/120V
GFCI Duplex
5-20R 120V
40.4 0
39.2 5 amps/receptacle
38.0 10 amps/receptacle
38.6 15 amps/receptacle
35.6 20 amps/receptacle
3Ø 240/480V
GFCI Duplex
5-20R 120V
70
0 amps/receptacle
65.8
5 amps/receptacle
61.7
10 amps/receptacle
57.5
15 amps/receptacle
53.4
20 amps/receptacle