Agilent 6800 series setup (continued)
Set the List points as follows:
List Vrms Dwell
Point Vrms frequency Slew Time
1 115 V 400 Hz INF *60 s
2 127 V 400 Hz INF 0.01 s
3 88 V 400 Hz 566 V/s 0.07 s
4 115 V 400 Hz INF *60 s
5 57 V 400 Hz INF 0.01 s
6 76 V 400 Hz 283 V/s 0.07 s
7 115 V 400 Hz INF *60 s
8 115 V 425 Hz INF 1 s
9 115 V 420 Hz INF 4 s
10 115 V 410 Hz INF 5 s
11 115 V 407 Hz INF 4 s
12 115 V 400 Hz INF *60 s
13 115 V 375 Hz INF 1 s
14 115 V 380 Hz INF 4 s
15 115 V 390 Hz INF 5 s
16 115 V 393 Hz INF 4 s
17 115 V 400 Hz INF *60 s
*
List points 1, 4, 7, 12, and 17 represent periods of time when the ac input to
the equipment under test is set to the nominal levels prior to the onset of the
next transient. The length of time the output of the ac power source/analyzer
is set to the nominal level can be determined by user-convenience (60 seconds
for this example).
Set the transient trigger source to BUS.
Initiate the transient trigger.
Enable the output of the ac power source/
analyzer.
Send a bus trigger.
Upon receipt of the trigger, the List sequence will
begin and the ac power source/analyzer output will
go to the setting represented in the first List step.
Each List step will be executed at the expiration
of the programmed dwell time of the previous step.
After the last List step is executed, the output of
the ac source will change to the immediate output
settings (Fixed mode settings).