Factory-Panel Lockout
WATLOW Series 988 User’s Manual 6.3
Factory Menus, Chapter 6
Panel Lockout Prompts
When you are in the Factory menus, the Series 988 displays the menu
selection ( [PLOC], [diAg] or [`CAL] ) in the upper display and [FctY] in
the lower display.
The Up-arrow > or Down-arrow key < selects another menu. Press the
Mode key µ to display the first prompt in the lower display and its value
in the upper display. Use the Up-arrow > and Down-arrow < keys to
change the value in the upper display. The new value will not take effect
until after a five-second delay or until you press the Mode key µ.
Front Panel Lockout
Sets the Lockout level for the Front Panel. This allows you to disable
keys on the front of the controller.
• [```0] enables all keys.
• [```1] disables the Mode key µ.
• [```2] disables the Mode key µ and the Auto/Man key å.
• [```3] disables the Mode key µ and the Auto/Man key å and locks
the set point value.
[`LOC] This prompt always appears.
Default
↓
[```0] [```1] [```2] [```3]
[`LOC] [`LOC] [`LOC] [`LOC]
ç
CAUTION:
Setting [`LOC] to
[```2] or [```3]
disables the
Auto/Man key å
and will force the
controller into man-
ual mode if an open
sensor occurs.
Verify that the con-
troller is operating
in the desired mode
(auto or manual)
before setting the
lockout level.
Failure to do so
could result in dam-
age to equipment
and or property.
[`LOC]
C6.wc 5/14/1999 8:52 AM Page 6.3