4.14 WATLOW Series 988 User’s Manual
Setup Menus, Chapter 4
Setup-Input
[CAL2]
[rtd2]
Calibration Offset 2
Offset the input 2 signal by a positive or negative value. This allows
you to compensate for lead resistance, sensor errors or other factors.
[CAL2] This prompt appears only if the controller is equipped with input 2
hardware and if [`In2] is not set to [``no] or [`Ei2].
If Minimum Default Max. setting/range
↓↓
[``°F] [-999] … [```0] … [`999]
[`C_F] [CAL2] [CAL2] [CAL2]
(Global Menu)
[``°F]
&
[`r†d] [-9(9] … [``)0] … [`9(9]
[`C_F] [`In2] [CAL2] [CAL2] [CAL2]
(Global Menu) (Input Menu)
[``°C] [-555] … [```0] … [`555]
[`C_F] [CAL2] [CAL2] [CAL2]
(Global Menu)
[``°C]
&
[`r†d] [-5%5] … [``)0] … [`5%5]
[`C_F] [`In2] [CAL2] [CAL2] [CAL2]
(Global Menu) (Input Menu)
[-999] … [```0] … [`999]
units
a process input
[CAL2] [CAL2] [CAL2]
is selected
RTD Calibration Curve 2
Select the calibration curve for the RTD 2 input. The RTD input uses
either the European (DIN, 0.003850Ω/Ω/°C) or Japanese (JIS,
0.003916Ω/Ω/°C) linearization standard.
[rtd2] This prompt appears only on controllers equipped with input 2
hardware and with [`In2] set to [`rtd] or [`r†d].
Default
↓
[`din] [`JIS]
[rtd2] [rtd2]
C4.wc 5/14/1999 8:48 AM Page 4.14