Watlow Electric 989 Weather Radio User Manual


 
WATLOW Series 988 User’s Manual 4.9
Setup Menus, Chapter 4
Setup-Input
˜
NOTE:
If [``no] is selected
for [`In2] none of
the other input 2
prompts will
appear.
Input 2
Select sensor type for input 2. This selection must match the sensor
type connected to terminals 18, 19 and 20. See Appendix for more infor-
mation about sensors.
• Changing the value of [`In2] changes all other prompts to the facto-
ry default values, except the Communications and Lockout menus,
the [`C_F] prompt in the Global Menu and the [`dFL] prompt in the
Calibration Menu. If you change the value, the default warning
[dFLt] will flash in the upper display.
• Changes do not take effect automatically after five seconds; you must
press the Mode key µ to enter the sensor type change and advance to
the next prompt.
[`In2] This prompt and other Input 2 prompts appear only on controllers
equipped with input 2 hardware (not 98_ _-_0_ _-_ _ _ _).
[`In2]
Input 2 continued
on next page.
[`In2]
If Default
↓ ↓
98_ _-1_ _ _-_ _ _ _
no DIP J K T N E W5 W3 Pt2 0-50mV
[``no] [```J] [```H] [```t] [```n] [```E] [```C] [```d] [`Pt2] [0-50]
thermocouple [``In2] [`In2] [`In2] [`In2] [`In2] [`In2] [`In2] [`In2] [`In2] [`In2]
only
98_ _-2_ _ _-_ _ _ _
Input 2 DIP J K T N E W5 W3 Pt2 0-50mV
[``no] [```J] [```H] [```t] [```n] [```E] [```C] [```d] [`Pt2] [0-50]
[`In2] [`In2] [`In2] [`In2] [`In2] [`In2] [`In2] [`In2] [`In2] [`In2]
thermocouple
Input 2 DIP
RSB
[``no] [```r] [```S] [```b]
[`In2] [`In2] [`In2] [`In2]
thermocouple
Input 2 DIP RTD RTD (0.1°)
[``no] [`rtd] [`r†d]
[`In2] [`In2] [`In2]
RTD
Input 2 DIP 4-20mA 0-20mA 0-5VÎ 1-5VÎ 0-10VÎ (dc)
[``no] [4-20] [0-20] [`0-5] [`1-5] [0-10]
[`In2] [`In2] [`In2] [`In2] [`In2] [`In2]
process
O
N
123
O
N
123
O
N
123
O
N
123
CAUTION:
Changing the value
of [`In2] changes
most other prompts
to the factory
default values.
Document all set-
tings before chang-
ing sensor type.
Verify the correct
sensor type before
making a change.
Failure to follow
this guideline could
result in damage to
equipment or prop-
erty. Document all
settings before
changing sensor
type.
C4.wc 5/14/1999 8:48 AM Page 4.9