Watlow Electric 989 Weather Radio User Manual


 
WATLOW Series 988 User’s Manual 4.39
Setup Menus, Chapter 4
Setup-Global
Crossover Process Value
Select the process value at which the control algorithm will crossover
between PID A and PID B. PID A is active below this value and PID B is
active above this value.
• This value cannot be set lower than range low 1 [`rL1] or higher than
range high 1 [`rH1].
[Proc] This prompt appears only on controllers with [Pid2] set to [Proc].
Default
[`rL1] [`rH1]
[Proc] [Proc]
Crossover Set Point Value
Select the set point value at which the control algorithm will
crossover between PID A and PID B. PID A is active below this value and
PID B is active above this value.
• This value cannot be set lower than range low 1 [`rL1] or higher than
range high 1 [`rH1].
[StPt] This prompt appears only on controllers with [Pid2] set to [StPt].
Default
[`rL1] [`rH1]
[StPt] [StPt]
[Proc]
[StPt]
C4.wc 5/14/1999 8:48 AM Page 4.39