Raypak 105B Swimming Pool Heater User Manual


 
HIGH WIND CONDITIONS
(OUTDOOR UNITS ONLY)
In areas where high winds are frequent, it may be
necessary to locate the heater a minimum of 3' from high
vertical walls, or install a wind break so the heater is not
in direct wind current.
In areas of daily high winds, it may be necessary to
replace the outdoor stackless top with a stack adapter in
combination with a wind resistant/weather proof outdoor
stack. See illustration below.
The outdoor stack serves the same function as the
low profile stackless top and should be installed in
accordance with the same clearance requirements.
9
INDOOR HEATERS
The design is certified by A.G.A. for indoor installa-
tion when equipped with the approved draft hood.
Locate heater as close as practical to a chimney or gas
vent. Heater must always be vented to the outside. See
Vent Piping Section for venting details. Minimum allow-
able space is shown on the nameplate.
COMBUSTION AIR (INDOOR UNITS ONLY)
Air For combustion And Ventilation
(Indoor Units Only)
The heater must have both combustion and venti-
lation air. Minimum requirements for net free air supply
openings, one 12 inches from ceiling for ventilation and
one 12 inches from the floor for combustion air as outlined
in the latest edition of the National Fuel Gas Code, Z223.1
and any local codes that may have jurisdiction.
CAUTION:
Combustion air must not be contaminated
by corrosive chemical fumes which can damage the
heater.
a. All Air From Inside The Building:
Each opening shall have a minimum of 105 net free
square inches.
b. All Air From Outdoors:
When air is supplied directly from outside of
building, each opening shall have a minimum of 27
net free square inches.
STACK ADAPTER
OUTDOOR STACK
Fig # 9253
INDOOR TOP
Fig # 9254