Omega Engineering CN9400 Weather Radio User Manual


 
FUNCTIONS MENU
Functions Menu
INSTRUMENT ADJUSTMENTS
To enter or exit program mode: Press ▲ ▼ together for 3 seconds
To scroll through functions: Press or
To change levels or options: Press ✱ ▲ together or ✱ ▼ together
To view setpoint: Press
To increase setpoint: Press ✱ ▲ together
To decrease setpoint: Press ✱ ▼ together
To reset an alarm or fault condition: Press ▲ ▼ together briefly
Notes: If in difficulty by becoming “lost” in program mode, press and
together for 3 seconds to return to display mode, check the
INSTRUMENT ADJUSTMENTS above and try again.
When in program mode, after 60 seconds of key inactivity
the display will revert to either
or, if the initial configuration has been completed, the
measured value. Any settings already completed will be retained.
Setpoint 1
Output
indicator
(green)
Process temperature (PV) or Function (green)
Setpoint temperature (SP) or Option (orange)
Setpoint 2 Output indicator (red)
BAND INT.T DER.T DAC CYC.T OFST SP.LK SPRR SPRN SOAK SET.2 BND.2 CYC.2
LEVL 1
TUNE
Autotune or Park
oFF; on; tunE; ParK; At.Sp
SP1 Prop band (gain)/hyst
0.1 deg to 25% sensor f/s
(10°C/18°F)
Integral time (reset)
Off; 0.1 to 60 min (5 min)
Derivative time (rate)
Off; 1 to 200 sec (25 sec)
Derivative approach
0.5 to 5.0 x bAnd (1.5)
Cycle time or on/off
On.off; 0.1 to 81 sec
(20 sec)
Offset (manual reset)
0 to 50% x bAnd
(In.t = off)
Setpoint lock (SP1)
Off; on
Setpoint Ramp rate
0 to 9990 deg/hour
Ramp off/on
On; off; hold
Soak time
Off; 0 to 1440 min
Adjust SP2 setpoint
+/– sensor full scale or
full scale
SP2 prop band/Gain/Hyst
0.1 deg to 100% sensor
f/s (2°C/3.6°F)
SP2 Cycle on/off
On.off; 0.1 to 81 sec
SP1 SETTINGS
BAUD DATA DBUG
LEVL C
ADDR
Instrument address
0 to 255
Baud rate
1200: 2400: 4800:
9600: 19k2
Data format
18n1:18E1:18O1
Tx/Rx activity
Off; on
COMMS SETTINGS
PROGRAMMER SETTINGS SP2 SETTINGS
HAND PL.1 PL.2 SP2.A SP2.B DISP HI.SC LO.SC INPT UNIT
LEVL 2
SP1.P
Read SP1 output %
0 to 100% read only
SP1 manual output %
0 to 100% proportional
mode only
Limit SP1 output %
100 to 0%
Limit SP2 output %
100 to 0%
Main SP2 mode
nonE; dV.hi; dV.Lo; bAnd;
FS.hi; FS,Lo; Cool
Second SP2 mode
nonE; LtCH; hold; Lt.ho;
nLin
Display resolution
1 or 0.1 degree
Set scale maximum
0.0 Sensor max to
sensor full scale
Set scale minimum
0.0 Sensor min to sensor
full scale
Select input sensor
nonE
Select display units
nonE; °C; °F; bAr;
PSi; Ph; rh; SEt
MANUAL ADJUSTMENTS SP2 MODES RANGING CONFIGURE INPUT
SP2.D BURN REU.D REU.L SPAN ZERO CHEK READ TECH UER RSET
LEVL 3
SP1.D
SP1 output device
nonE; rlY; SSd
*
SP2 output device
nonE; SSd; rlY (read only)
*
Sensor burn-out
uP.SC; dn.SC; 1u.2d; 1d.2u
Reverse outputs
1r.2d; 1d.2d; 1r.2r; 1d.2r
Reverse O/P LEDs
1n.2n; 1i.2n; 1n.2i; 1i.2i
Span adjustment
0.0 to 25% sensor f/s
Zero Adjustment
0.0 to 25%
sensor full scale
Set Monitor
Off; on
Read Monitor
VAr; hi; lo deg
Read Tune Data
CtA; Ctb; Ct1; Ct2; Ct3;
Ct4; oS1; uS; oS2
Software version
Consult unit
RESET
nonE; ALL
CONFIGURE OUTPUT SAFETY SETTINGS CALIBRATION PERFORMANCE DATA
PROG NO.AL DIS.S DER.S
LEVL 4
LOCK
Security lock
nonE; LEV 3; LEV 2; ALL
Disable program auto-exit
Auto; StAY
Disable -AL- alarm display
Off; on
Display averaging
dir; 1 to 32 (6)
Derivative sensitivity
0.1 to 1.0 x dEr.t (0.5)
USER-PROTECTED SETTINGS
PROGRAM ENTRY
Level C only visable
when COMMS
Option fitted
QUICK START ENTRY
KEY ▼ ▲ TO VIEW FUNCTIONS
KEY ✱ ▼ OR ✱ ▲ TOGETHER TO CHANGE LEVELS OR OPTIONS
Range of Adjustment shown in red under
description. If applicable, factory settings shown
in bold.
* Note: Dual Relay and Dual SSd Output Options
Models CN9411 and CN9422 have their outputs
pre-configured. (see page 22)
A3
INPT
NONE