Omega Engineering CN9400 Weather Radio User Manual


 
Function List
Sensor burn-out/break protection
Caution: Settings affect fail safe state.
SP1 SP2
[uP.SC]
Upscale Upscale
dn.SC
Downscale Downscale
1u.2d
Upscale Downscale
1d.2u
Downscale Upscale
Select output modes: Direct/Reverse
Caution: Settings affect fail safe state.
SP1 SP2
[1r.2d]
Reverse Direct
1d.2d
Direct Direct
1r.2r
Reverse Reverse
1d.2r
Direct Reverse
Select Reverse on SP1 for heating and Direct for
cooling applications.
19
LEVEL 3
OUTPUT CONFIGURATION
Note: ‘Read only’ after initial configuration.
rSET ALL
full reset to
factory settings required to change subsequently.
Function Options
[Factory settings] shown in brackets
[nonE] rLY SSd rLY1 rLY2 SSd1
Select SP1 output device
[nonE] SSd rLY rLY2 rLY1 SSd2
Read SP2 output device
(read only)
Dual Relay and Dual SSd output options Models CN9411
and CN9422 are factory set. See page 22
Note: (when in initial configuration only)
Hold and or for 10 seconds to move to or from
output devices in shaded portion.
SP1.D
BURN
REU.D
SP1.D
SP2.D