Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 Portable Generator User Manual


 
28 Generac
®
Power Systems, Inc.
Section 4 — Troubleshooting
Guardian Air-cooled Generators
4.2 INSTALLATION CHECKLIST
BATTERY INSTALLATION
Battery is connected properly.
Recommended battery is installed.
Cables are clean and tight.
Terminals are coated with anti-corrosion grease,
and terminal covers are positioned.
FUEL SYSTEM
Complies with local and NFPA codes.
Fuel is connected and checked for leaks.
Correct fuel pressure (11-14 inches of water
(0.6 psi) at all load ranges).
Load block adjusted for maximum power for
natural gas fuel.
LOCATION
Unit is fastened to the appropriate mounting pad.
Louvers are free from obstruction.
Exhaust is clear of flammable objects and debris.
ELECTRICAL CONNECTIONS
Complies with local code requirements and all
National Electrical Codes.
Utility is connected and present.
Transfer switch is connected.
All wires running outside of the generator are in
NEC-approved conduit. *Note: Utility wires and
transfer switch control wires must be in separate
conduit.
Unit is grounded to an approved earth ground.
COOLING AND VENTILATING
All inlets and outlets are free from obstruction.
See Figure 1.4 and Figure 1.5.
OTHER
Verify that the unit is filled to the proper level with
the proper break-in oil. Adjust as required.
Notify owner that the “Break-in Procedure” should
be performed. Refer the owner to the Owner’s
Manual shipped with the unit.
OPTIONS AND ACCESSORIES
Control board is configured properly. See
Section 1.15.
Remote alarm is installed if desired. See
Section 2.6.
Remote start is installed if desired. See
Section 2.6.