Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 Portable Generator User Manual


 
24 Generac
®
Power Systems, Inc.
3.7 ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly
high or low, adjust the engine governor as follows:
3.7.1 6 KW UNITS (NON-SA)
1. Loosen the governor clamp bolt (Figure 3.1).
2. Push the spring end of the governor lever clock-
wise to the wide open throttle position of
the lever.
Hold the governor lever at wide open throttle and,
with a pair of pliers, rotate the governor shaft
fully clockwise.
While holding the governor shaft fully clockwise
and the governor lever at wide open throttle,
tighten the governor clamp bolt to 70 inch-
pounds (8 N-m).
3. Start the engine; let it stabilize and warm up at
no-load.
4. Turn the adjuster nut to obtain a frequency read-
ing of 62 Hertz.
5. Determine if the governor spring is properly
located in the slot of the governor lever as
follows:
If droop is excessive, move the governor spring
down one slot on the lever.
For greater stability, move the governor spring up
one slot on the lever.
6. After repositioning the spring on a lever slot,
recheck the frequency reading and, if necessary,
readjust the adjuster nut to obtain 62 Hertz at
no-load.
7. When frequency is correct at no-load, check the
AC voltage reading. If voltage is incorrect, the volt-
age regulator may require adjustment.
Figure 3.1 – 6 kW
Engine Governor Adjustment
3.7.2 8 KW AND 10 KW UNITS (NON-SA)
1. Loosen the governor clamp bolt (Figure 3.2).
2. Push the spring end of the governor lever clock-
wise to the wide open throttle position of
the lever.
Hold the governor lever at wide open throttle
and, with a screwdriver, rotate the governor
shaft fully clockwise.
• Before tightening, verify that the governor lever is
pushed all the way onto the governor shaft.
While holding the governor shaft fully clockwise
and the governor lever at wide open throttle,
tighten the governor clamp bolt to 70 inch-
pounds (8 N-m).
3. Start the engine; let it stabilize and warm up at
no-load.
4. Turn the speed adjust nut to obtain a frequency
reading of 62 Hertz.
5. When frequency is correct at no-load, check the
AC voltage reading. If voltage is incorrect, the volt-
age regulator may require adjustment.
Figure 3.2 – 8 kW and 10 kW
Engine Governor Adjustment
NOTE:
If the engine continues to run fast, use a pair of
pliers to bend the bend tab clockwise to release
tension on the lower governor spring.
Section 3 — Post-installation Start-up Adjustments
Guardian Air-cooled Generators