Generac 13694330200 Portable Generator User Manual


 
Maintenance
Maint
Maintenance
Maintenance
Tasks
Task
Completed
Level
Interval
Date/Initials
1.
Disable
the
unit
from
operating
per
the
first
page
warning.
2.
Check
the
engine
oil
level.
Adjust
as
necessary.
3.
Check
the
engine
coolant
level.
Adjust
as
necessary.
4.
Check
the
battery
electrolyte
level
if
accessible.
Adjust
as
necessary.
Every
6
months
or
5.
Check
the
diesel
fuel
supply
level.
Adjust
as
necessary.
50
hours
of
operation
2
6.
Drain
water
and
sediment
from
the
diesel
fuel
tank.
(Requires
approximately
7.
Drain
water
from
the
diesel
fuel
line
water
separator
if
unit
is
equipped
1.5
man
hours
with
one.
per
unit)
8.
Check
the
air
inlets
and
outlets
for
debris.
Clean
as
necessary.
9.
Visually
inspect
the
unit
looking
for
leaks,
wear
or
damage,
loose
con-
nections
or
components,
and
corrosion.
Correct
as
necessary.
10.
Initiate
an
automatic
start
and
transfer
to
load
of
the
unit,
and
exer-
cise
it
for
at
least
1
hour
looking
for
leaks,
loose
connections
or
com-
ponents,
and
abnormal
operating
conditions.
Correct
as
necessary.
11.
Return
the
unit
to
standby
setup
for
operation
when
required.
Technician's
Signature
Date
Inspection
Completed
Unit
Hour
Meter
Reading
at
Completion
of
the
Inspection
23