6.4 WATLOW Series 988 User’s Manual
Factory Menus, Chapter 6
Factory-Panel Lockout
System Menu
Select the lockout level for the System Menu. Set the System Menu
lockout to no lockout [none], read only [read] or full lockout [FULL].
[`LOC] This prompt always appears.
Default
↓
[none] [read] [FULL]
[`SYS] [`SYS] [`SYS]
PID A Menu
Select the lockout level for the PID A Menu. Set the PID A Menu lock-
out to no lockout [none], read only [read] or full lockout [FULL].
[PidA] This prompt always appears.
Default
↓
[none] [read] [FULL]
[PiDA] [pida] [pida]
PID B Menu
Select the lockout level for the PID B Menu. Set the PID B Menu lock-
out to no lockout [none], read only [read] or full lockout [FULL].
[PidB] This prompt appears only on controllers with enhanced software
(98_B-_ _ _ _-_ _ _ _) and with [ALgO] (Global Menu) set to [Pid2] or
[CntL] (Global Menu) set to [CSCd].
Default
↓
[none] [read] [FULL]
[PiDb] [pidb] [pidb]
[PidA]
[PidB]
[`SYS]
The prompts within the Panel Lockout Menu allow you to lockout an
entire menu. You can set the level of lockout to none [nonE], read only
[rEAd], or lockout read and write [FULL].
C6.wc 5/14/1999 8:52 AM Page 6.4