Watlow Electric 986 Weather Radio User Manual


 
WATLOW Series 988 User’s Manual 4.27
Setup Menus, Chapter 4
Setup-Output
Latching 3
Select whether alarm 3 will be latching or non-latching. A latching
alarm [`LAt] must be turned off manually. A non-latching alarm [`nLA]
turns off when an alarm condition no longer exists.
[LAt3] This prompt appears only on controllers equipped with output 3
hardware for a relay (98_ _-_ _ _ _-B_ _ _, 98_ _-_ _ _ _-J_ _ _ or
98_ _-_ _ _ _-K_ _ _) or switched dc (98_ _-_ _ _ _-C_ _ _) and with [`Ot3] set
to [`AL3] or [AL3n].
Default
[`nLA] [`LAt]
[LAt3] [LAt3]
Silencing 3
Select silencing to inhibit alarm 3 on startup and to allow the opera-
tor to reset the alarm output, not the visual display.
• Silencing disables the alarm until the signal is between [A3LO] and
[A3HI].
[SIL3] This prompt appears only on controllers equipped with output 3
hardware for a relay (98_ _-_ _ _ _-B_ _ _, 98_ _-_ _ _ _-J_ _ _ or
98_ _-_ _ _ _-K_ _ _) or switched dc (98_ _-_ _ _ _-C_ _ _) and with [`Ot3] set
to [`AL3] or [AL3n].
Default
[`OFF] [``On]
[SIL3] [SIL3]
˜
NOTE:
See Chapter 7 for
more information
on alarms.
[LAt3]
˜
NOTE:
See Chapter 7 for
more information
on alarms.
[SIL3]
C4.wc 5/14/1999 8:48 AM Page 4.27