Shindaiwa DG1000MI Portable Generator User Manual


 
- 33 -
<Caution>
Do not drive the starter motor for more than 10 seconds successively
If you need to restart, wait at least 30 seconds before the retry.
Release the starter switch, as soon as the engine is started
Keep the engine idle for at least 5 minutes
Set the throttle lever to RUN. Ensure that the frequency meter shows the following
frequency at no load.
<Caution>
In either case of incorrect frequency or frequency change, adjust the frequency by
FREQUENCY ADJUST SCREW.
By setting frequency to the above frequency under no load, 50 or 60Hz(almost) will
be obtained at the rated output load.
Adjust to the required voltage by adjusting Voltage regulator.
50Hz Operation 200V
60Hz Operation 220V
Turn the circuit breaker to ON position to send power to the load side.
:Electrical Shock Injuries
Before turning the circuit breaker to ON position to send power to the load side, always
ensure that any circuit breaker and switch of loads are positioned to OFF.
In the case the generator and the load are away from each other, proceed with the Above
steps, communicating well with the other person by the load in order to prevent from
accident.
No-load frequency(Revolution)
50Hz Operation 52.5Hz 1575min
-1
60Hz Operation 63.0Hz 1890min
-1