Subaru Robin Power Products RGXI 800 Portable Generator User Manual


 
11-4 NO DC OUTPUT
0
11-4-l CHECK THE AC OUTPUT.
Check the generator by following Step 11-1-l through Step 11-1-3.
1 l-4-2 CHECK THE DC FUSE.
Check the fuse in the fuse holder.
If the fuse is blown, check for the cause of fuse
blowing, and then replace with a new one.
FUSE : 10A
FUS
NOTE: If the DC output is used to charge a
large capacity battery or an overdis-
charged battery, an excessive current
may flow causing fuse blow.
1 l-4-3 CHECK THE WIRING.
Check all the wires to be connected correctly.
1 l-4-4 CHECK THE DIODE RECTIFIER.
Remove the control panel and check the diode
rectifier with a circuit tester.
Refer to Section 9-7 “DIODE RECTIFIER” for the
checking procedure.
11-4-5 CHECK THE DC COIL
Fig. 11-11
Check the resistance between two brown leads from stator with a circuit tester.
MODEL
SPECIFICATION RESISTANCE
50Hz
RGXl800
11 OV, 22OV, 24OV, 11 OVl22OV
0.41 !a
60Hz 12OV, tiOV, 11 OVl22OV, 12OV/24OV 0.3552
I
50Hz
RGX2400 -
11 OV, 22OV, 24OV, 11 OVl22OV
0.298
60Hz
12OV, 22OV, 11 OV/22OV, 12OVl24OV 0.278
50Hz
RGX3!500
11 OV, 22OV, 24OV, 11 OVl22OV 0.26R
60Hz 12OV, 22OV, 11 OVl22OV, 12OVl24OV 0.2251
50Hz
RGX5!500
11 OV, 22OV,
24OV,
11 OVl22OV 0.1552
60Hz 12OV, 22OV, 11 OVl22OV, 12OVl24OV 0.1452
0
Table 1 l-3
If the resistance reading is much larger or smaller than the specified value, the DC coil of the stator is
faulty. Replace stator with a new one.