DCA-600SSV — GENERATOR SHUT-DOWN PROCEDURE
Normal Shutdown Procedure
To shutdown the generator use the following procedure:
1. Place both the GFCI and AUX circuit breakers as shown
in Figure 42 to the OFF position.
2. Place the engine speed switch (Figure 65) in the
LOW ” (down) position.
Figure 66. MPEC Control Switch (Off/Reset)
5. Press the
main
circuit
breaker “OFF” switch (Figure 40).
6. Verify that the
main
circuit
breaker “OFF” lamp (Figure 41)
is lit (ON).
7. Verify that the
all
status LED on the MPEC display
are OFF (not lit).
8. Remove all loads from the generator.
9. Inspect entire generator for any damage or loosening of
components that may have occured during operation.
3. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
4. Place the
MPEC Control Switch
(Figure 66) in the
OFF/RESET position.
Figure 65. Engine Speed Switch (Low)
NEVER stop the engine suddenly except in an emergency.
WARNING -
SHUTTING DOWN THE GENERATOR
Emergency Shutdown Procedure
1. PUSH inward the emergency stop button located on the
engine operating panel
(Figure 67) to turn off the
generator in the event of an emergency.
Figure 67. Emergency Stop Button
EMERGENCY
STOP
PUSH
TO STOP