Multiquip DCA-600SSV Portable Generator User Manual


 
PAGE 28 — DCA-600SSV — OPERATION AND PARTS MANUAL — REV. #0 (07/13/09)
Figure 12. Connecting Loads
Connecting Loads
Loads can be connected to the generator by the UVWO terminal
lugs or the convenience receptacles. (See Figure 12). Make
sure to read the operation manual before attempting to connect
a load to the generator.
To protect the UVWO output terminals from overload, a 3-
pole, 1,600 amp,
main
circuit breaker is provided. Make
sure to switch
ALL
circuit breakers to the "OFF" position
prior to starting the engine.
DCA-600SSV — OUTPUT TERMINAL PANEL FAMILIARIZATION
Over Current Relay
An
over current relay
(Figure 13) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the
reset button
on the over cur-
rent relay must be pressed. The over current relay is lo-
cated in the control box.
Figure 13. Over Current Relay
Maximum Power Output (KW)
The entire load connected to the UVWO output terminal lugs,
duplex and auxiliary receptacles must not exceed 528 kW in
standby or 480 kW in prime output.