When starting generator in AUTO mode use the "
Manual
Start-up" procedure except where noted (see below).
1. Perform steps 1 through 4 in the
Before Starting
section
(page 38) as outlined in the
Manual Starting
Procedure
.
Figure 63. Engine Speed Switch (High)
Figure 64. Off/Manual Auto Switch (AUTO)
4. Place the Off/Manual/Auto switch (Figure 64) on the
MPEC unit to the AUTO position.
NOTE
When the generator is set in the “
AUTO ” mode, the generator will
automatically start
in the event of
commercial power falling below a
prescribed level by means of a
contact closure that is generated
automatically by a transfer switch.
2. Set the
battery ON/OFF switch
(Figure 62) to the “ON
position.
Figure 62. Battery ON/OFF Switch
3. Set the engine speed switch (Figure 63) to the “High
position.
5. Press the circuit breaker
ON Switch
(Figure 58).
6. Verify that the circuit breaker on lamp (Figure 59) is lit.
7. Continue operating the generator as outlined in the
Manual Start-up
procedure (start at step 10).
Before connecting this generator to any
building’s electrical system, a
licensed
electrician
must install an
isolation
(transfer)
switch
. Serious damage to the
building’s electrical system may occur
without this transfer switch.
DANGER - ELECTRICAL SYSTEM HAZARDS
When running the generator in the AUTO mode, remember
the generator can start up at any time without warning.
NEVER attempt to perform any maintenance when the
generator is in the auto mode.
WARNING - AUTO MODE MAINTENANCE
When connecting the generator to a isolation (transfer)
switch, ALWAYS have power applied to the generator's
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
CAUTION - BACKUP GENERATOR USE
The
Engine Speed Switch
must be set to the "High"
position when running in the
Auto-Start
mode. Failing to
set the switch in the proper position can result in damage
to your generator when it turns on.
CAUTION - ENGINE SPEED SWITCH
DCA-600SSV — GENERATOR START-UP PROCEDURE (AUTO MODE)
23. Observe the generator's ammeter (Figure 61) and verify
it reads the anticipated amount of current with respect
to the load. The ammeter will only display a current
reading if a load is in use.
24. The generator will run until manually stopped or an
abnormal condition occurs.
Figure 61. Ammeter (Load)