Reference Manual
00809-0200-4801, Rev BA
April 2007
Rosemount 3051S
3-8
1. Process Anomaly Detected (SPM)
2. LOI Failure
3. PWA Simulate Active
4. Defer NV Memory Write Detected
5. Mass Flow Transducer Block Reverse Flow
6. Mass Flow Transducer Block Sensor Out of Range
7. Mass Flow Transducer Block Out of Range
8. Process Anomaly Detected (SPM)
ADVISE_MASK
The ADVISE_MASK parameter will mask any of the failed conditions listed
in ADVISE_ENABLED. A bit on means the condition is masked out from
alarming and will not be reported.
ADVISE_PRI
ADVISE_PRI designates the alarming priority of the ADVISE_ALM, see
“Process Alarms” on page 3-15. The default is 0 and the recommended
values are 1 or 2.
ADVISE_ACTIVE
The ADVISE_ACTIVE parameter displays which of the advisories is active.
Only the advisory with the highest priority will be displayed. This priority is
not the same as the ADVISE_PRI parameter described above. This priority
is hard coded within the device and is not user configurable.
ADVISE_ALM
ADVISE_ALM is an alarm indicating advisory alarms. These conditions do
not have a direct impact on the process or device integrity.
Recommended Actions for PlantWeb Alarms
RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that will give
a recommended course of action to take based on which type and which
specific event of the PlantWeb alarms is active (See Table 5-12 on page 5-10).
ANALOG INPUT (AI)
FUNCTION BLOCK
Configure the AI block A minimum of four parameters are required to configure the AI Block. The
parameters are described below with example configurations shown at the end of
this section.