Reference Manual
00809-0200-4801, Rev BA
April 2007
3-29
Rosemount 3051S
Establish Communications with the 3051S FOUNDATION Fieldbus
Transmitter using 3095 EA for F
OUNDATION Fieldbus
1. Connect the 9-pin communications cable into the PCMCIA card port
located in the computer.
2. Connect communication wiring to the cable connectors labeled “D
+
”
and “D
-
”.
3. Open the transmitter cover on the side marked “Field Terminals”.
Connect the communication wires to the 3051S transmitter terminals
labeled “Fieldbus Wiring”.
4. Verify device is properly powered to establish communications.
5. Open the 3051S Engineering Assistant for F
OUNDATION Fieldbus
program. Select the 3051S Engineering Assistant for F
OUNDATION
Fieldbus from the program menu or use the 3051S EA for FF shortcut
icon.
6. Select Scan to scan the F
OUNDATION Fieldbus segment. Scanning will
locate and present live 3051S or 3095 F
OUNDATION Fieldbus
transmitters on the segment that has a licensed mass flow block. The
transmitter device tag name will appear on the screen in the Device
view. The Device Status view will publish the status of the transmitter.
7. F
OUNDATION Fieldbus communication status is represented in the
lower right corner of the screen. If status is ONLINE, communication
has been established. If status is OFFLINE, communication has not
been established and/or communication has been disconnected.
Figure 3-7. Device View
Scan
fieldbus
Segment
3051S Device Tag
Name(s) on Segment
Selected Device
Status
Communication Status
ONLINE or OFFLINE