Reference Manual
00809-0200-4801, Rev BA
April 2007
3-19
Rosemount 3051S
DISPLAY_PARAM_SEL
The DISPLAY_PARAM_SEL parameter specifies how many process
variables will be displayed. Select up to four display parameters.
BLK_TAG_#
(1)
Enter the Block Tag of the function block that contains the parameter to be
displayed.
BLK_TYPE_#
(1)
Enter the Block Type of the function block that contains the parameter to be
displayed. This parameter is generally selected via a drop-down menu with a
list of possible function block types. (e.g. Transducer, PID, AI, etc.)
PARAM_INDEX_#
(1)
The PARAM_INDEX_# parameter is generally selected via a drop-down
menu with a list of possible parameter names based upon what is available in
the function block type selected. Choose the parameter to be displayed.
CUSTOM_TAG_#
(1)
The CUSTOM_TAG_# is an optional user-specified tag identifier that can be
configured to be displayed with the parameter in place of the block tag. Enter
a tag of up to five characters.
UNITS_TYPE_#
(1)
The UNITS_TYPE_# parameter is generally selected via a drop-down menu
with three options: AUTO, CUSTOM, or NONE. Select AUTO only when the
parameter to be displayed is pressure, temperature, or percent. For other
parameters, select CUSTOM and be sure to configure the
CUSTOM_UNITS_# parameter. Select NONE if the parameter is to be
displayed without associated units.
(1) _# represents the specified parameter number.
Display Parameter 1
Block Type #1
AI Block
FFAI_RMT3
OUT
Auto
Block Tag #1
Param Index #1
Custome Tag #1
Units Type #1
Custom Units #1