Emerson 3051S Lawn Mower User Manual


 
Reference Manual
00809-0200-4801, Rev BA
April 2007
3-31
Rosemount 3051S
Figure 3-9. EA Wizard View
4. Upon completing a mass flow configuration using the EA Wizard, the
file can be saved to disk. The file must be saved for review or to edit
the mass flow configuration file in the future. F
OUNDATION Fieldbus
mass flow configuration files cannot be uploaded from the Mass Flow
Transducer Block. If the file is not saved, it cannot be retrieved.
5. Select the “Send” button to download the mass flow configuration file
to the Mass Flow Transducer Block. Sending the mass flow
configuration file will overwrite the existing file in the Mass Flow
Transducer Block. The transmitter must be out of service to send a
mass flow configuration file.
6. A message box will appear confirming the action to send the mass
flow configuration file to the Mass Flow Transducer Block. Select
“OK” to send the mass flow configuration file.
7. Completing the download of the file to the Mass Flow Transducer
Block, a screen that says “Installation Completed Successfully” will
appear. Select OK.
8. The installation is now complete and will appear in the Device Status
portion of the screen.
9. Bring the transmitter back into service using the host system, for
example DeltaV.
EA Wizard