8-2
AC
OUTPUT MEASURING
4
To
AC
receptacle
Fig.
8-8
Measurement is executed with the circuit as shown in Fig.
8-8.
An electric heater or an incandescent
lamp with a power factor of
1.0
is suitable
as
a load for the generator. When the AC output measured at
the rated load and rated speed
is
confirmed to be within the voltage range specified in the table below,
the AC output
is
normal.
I
Rated voltage
I
120v
I
Voltage range
1
17-1
30V
Table
8-2
8-3
DC
OUTPUT MEASURING
I
To
DC
Terminal
-l
I
P
Fig.
8-9
Measurement of DC output
is
executed with the switch turned
ON
while the current is regulated at 8.3A
by adjusting the load to the generator.
If
the voltage is within the range from
6V
to
14V,
the voltage
output is normal.
Note
:
If
a
battery is connected
as
a
load to the generator, the
DC
output voltage will increase by
approximately
I
to
2V.
Therefore, carefully observe the electrolyte level and do not overcharge
the battery.
-