Basic Hardware and Function 153
7. Instructions
FUN 041 DIV Unsigned double/single division
Expression
Input [ A+1A DIV B C ] Output
Function
When the input is ON, the double-word data of A+1A is divided by the data of B, and the quotient
is stored in
C
and the remainder in
C+1.
The data range of
A+1
A
is 0 to 4294967295, and the data
range of
B
and
C
is 0 to 65535.
If the quotient is greater than 65535 (overflow), the limit value 65535 is stored in
C
, 0 is stored in
C+1, and the instruction error flag (ERF = S051) is set to ON.
Execution condition
Input Operation Output ERF
OFF No execution OFF
ON
Normal execution (B 0)
ON
Overflow (B 0)
ON Set
No execution (B = 0)
OFF Set
Operand
Name Device Register Constant Index
X Y R S T. C. XWYWRWSW T C D I J K
A Dividend
√√√√√√√
B Divisor
√√√√√√√
C Quotient
√√√√√√
Example
When R010 is ON, the double-word data of D0201D0200 is divided by the constant data
4000, and the quotient is stored in D1000 and the remainder is stored in D1001.
If the data of D0201D0200 is 332257, the quotient 83 is stored in D1000 and the remainder
257 is stored in D1001.
D0201D0200 332257
÷
D1000 83 (quotient)
Constant 4000 D1001 257 (remainder)
Note
If divisor (operand B) is 0, ERF (instruction error flag = S051) is set to ON.
The ERF (S051) can be reset to OFF by user program, e.g. [ RST S051 ].
This instruction handles the register data as unsigned integer.