Selection of cable
(
Example) 220V and Voltage Drop 11V
3-Phase 3-Wire Cap Tire Cable, Single Core
(Unit: mm
2
)
Length
Current
50m or
below
75m 100m 125m 150m 200m
20A 3.5 5.5 8 8 14 14
40A 8 14 14 14 22 22
60A 14 14 22 22 30 38
80A 14 22 22 30 38 50
(Example) 100V and Voltage Drop 5V
1-Phase 2-Wire Cap Tire Cable, Single Core
(Unit: mm
2
)
Length
Current
50m or
below
75m 100m
10A 5.5 5.5 8
20A 8 14 22
30A 14 22 22
7.2 Connecting Cable
!
Danger
:Electrical Shock
Before connecting or disconnecting a load cable from output terminals, always turn a circuit breaker to
OFF position, stop the engine, and remove the engine key. A person performing the maintenance
should always keep the key.
!
Caution
:Fire
Do not connect AC output to any indoor wiring.
<Caution>
Divide loads into 3 circuits proportionally as possible, when using the maximum output power especially,
and connect them to each phase (R,S,T) respectively.
Be careful to limit the current under the rated current per the phase .
The 1-Phase terminals and receptacles output power are originated from the R and T Phase output
powers.