When the water temperature reaches 110 degrees Celsius during operation,
the water temperature-monitoring lamp will flash, and the automatic shutoff will be engaged.
When this occurs, check the Coolant reservoir tank, and replenish if needed
(refer to 8-2 Checking coolant / water level).
If the water level is normal, check for loose fan belt or possible water leak in the cooling system,
after the engine is cooled down.
<Caution>
If the water level is too low, the sensor cannot detect the water temperature. Be sure
to check the water level in the radiator and the Coolant reservoir tank prior to operating
the equipment.
5.1.2 Engine Oil Monitoring Lamp (for oil pressure low)
!
Danger
: Injuries
Close all doors and place locks during operating this equipment, to avoid injuries by
unintentionally touching cooling fan and fan belt.
!
Caution
: Burns
Do not touch the engine and muffler during operation and immediately after stopping
the equipment, for the temperature can reach extremely high.
When checking engine oil or changing oil, always stop the engine, and wait until the
engine cools down. If you open either the oil gauge or the oil filler cap during operation,
hot oil may cause some injury.
When the engine oil pressure drops below 0.98 x 100kPa (1kgf/cm
2
) during operation,
the oil pressure monitoring lamp will flash, and the automatic shutoff will be engaged.
When this occurs, check the engine oil level, and replenish to the maximum level if needed
<Caution>
The engine oil pressure monitor cannot detect the degradation of engine oil itself. Please check
the engine oil periodically, and change if needed (refer to 8-1 Checking Engine Oil).