Characteristics (continued)
0
IP 67 modular I/O splitter boxes
for fieldbuses 0
Advantys
Distributed I/O, FTM splitter boxes
Digital input/output splitter box characteristics
Splitter box type Inputs Inputs/outputs
Compact FTM 1DE08Cpp FTM 1DE16C12 FTM 1DD08Cpp FTM1DD16C12
Expandable FTM 1DE08CppE FTM 1DE16C12E FTM 1DD08CppE FTM 1DD16C12E
Number of inputs/outputs
8I 16 I 8 I/O 16 I/O
Internal consumption of splitter box
mA 30 (M8)
50 (M12)
50 30 (M8)
50 (M12)
50
Operating voltage
c V 24
Splitter box max. supply current
A 4
Auxiliary supply max. current
A 4 (only
FTM 1DD16C12)
Bus and I/O undervoltage detection
V <18
Input characteristics
Number of inputs 8I 16 I 0...8 I 0...16 I
Conformity to IEC 1131-2
Type 2
Compatibility with 2-wire/3-wire
proximity sensors
Yes
Input values Nominal voltage
c V 24
Maximum current
mA 200
Sensor power supply
V 18...30
Logic
Positive
Input filtering
ms 1
Channel status indication
By LED (yellow), one LED per input
Protection against reversed polarity
Yes
Output characteristics
Number of outputs 0...8 O 0...16 O
Output type
Transistor
Nominal output values Voltage
c V 24
Current
A 0.5
Response time
ms <0.5
Max. switching cycle
Hz Resistive: 50
Inductive: 5
Max. lamp load
W 10
Channel status indication
By LED (yellow), one LED per output
Output connection/cable lengths
0.34 mm
2
/ 5 m (#22 AWG / 16.4 ft.) max
0.75 mm
2
/ 10 m (#19 AWG / 32.8 ft.) max
Analog input/output splitter box characteristics
Splitter box type Inputs Outputs
Compact FTM 1AE04C12C FTM 1AE04C12T FTM 1AS04C12C FTM 1AS04C12T
Number of inputs/outputs
4I 4I 4O 4O
Internal consumption of splitter box
mA 50
Operating voltage
c V 24
Maximum supply current Splitter box
A 4
Per channel
A 0.2 1.6
Bus and I/O undervoltage detection
V <18
Input and output characteristics
Type Differential 300 Ω Differential 1 MΩ 500 Ω 500 Ω
Current Measuring range
0 to 20 mA, 4 to
20 mA
c ±10V, c 0 to
10 V
0 to 20 mA, 4 to
20 mA
c ±10V, c 0 to
10 V
Resolution
Bits 16 15 + Sign 12 11 + Sign
Conversion time
ms 2/channel 1/channel
Input filtering
ms 1
Channel status indication
By LED
Output connection/cable lengths
m (ft.) 30 (98.4) max.
Digital and analog splitter boxes diagnostic characteristics
Internal bus and I/O undervoltage detection V <18
Internal bus communication
By LED
Channel and splitter box short-circuit
By LED
Cable breakage
By LED