0
IP 67 monobloc I/O splitter boxes
for fieldbuses 0
Advantys
Distributed I/O, FTB splitter boxes
Input/output characteristics
Splitter box type FTB 1pp16Epp 1pp08E08SPp 1pp12E04SPp 1pp16Cpp 1pp08E08CM0
Bus type
All types of bus CANopen bus,
DeviceNet bus
and Profibus-DP
bus
Number of inputs/outputs
16 I
(8 I +
8 diagnostic
inputs)
16 I/O
(8 O +
8 diagnostic
inputs)
16 I/O
(4 I + 4 O +
8 diagnostic
inputs)
16 I/O
(8 I/O +
8 diagnostic
I/O)
8 I + 8 I/O
(8 I + 8 diagnostic
I/O)
Internal consumption of splitter box
mA 120
Operating voltage
c V 24
Splitter box max. supply current
A 9 (10 for InterBus)
Bus and I/O undervoltage detection
V < 18
Built-in short-circuit protection
mA < 100, automatic tripping
mA > 100, reset
Input characteristics
Number of inputs 16 I 8 I 12 I 0...16 I 8 I + 0...8 I
Conformity to IEC 1131-2
Type 2
Compatibility with 2-wire/
3-wire proximity sensors
Yes
Input values Nominal voltage
c V 24
Maximum current
mA 200
Sensor power supply
V 18 to 30
Logic
Positive
Input filtering
ms 1
Protection against reversed polarity
Yes
Output characteristics
Number of outputs 8 O 4 O 0...16 O 0...8 O
Output type
Transistor
Nominal output values Voltage
V c 24
Current
A 1.6
Overvoltage protection
Yes (suppressor diode)
Maximum switching cycles
Hz 20
Maximum lamp load
W 10
Output connection/cable lengths
mm
2
AWG
0.34 mm
2
/ 5 m (#22 AWG / 16.4 ft.) max.