Multiquip DCA-300SSK Portable Generator User Manual


 
DCA-300SSK SERIES — PARTS AND OPERATION MANUAL (STD)— REV. #4 (03/27/06) — PAGE 29
DCA-300SSK SERIES — GENERATOR OUTPUTS/GAUGE READING
How to Read the Output Terminal Gauge.
The AC ammeter and AC voltmeter change-over switches
on the control panel DO NOT effect the generator output.
They are provided to help observe how much power is being
supplied, produced at the UVWO terminals lugs.
When the voltage change-over board is jumpered for 3Ø,
240V operation (See Figure 15), place the
AC Voltmeter
Change-Over
Switch
(Figure 16) to the W-U position and
the
AC Ammeter Change-Over Switch
(Figure 18) to the U
or W position to read the output on the selected leg.
The
ammeter
and
voltmeter
gauges are only active when the
UVWO terminals are in use.
NOTE
Figure 15. Voltage Change-Over Board
240V Configuration
Maximum Amps
Table 10 shows the
maximum
amps the generator can pro-
vide. DO NOT exceed the maximum amps as listed.
spmAmumixaMrotareneG.01elbaT
:ledoM
KSS003ACD
seireS
egatloVdetaRspmAmumixaM
esahPelgniS
tloV021
)eriw4(spma0002
esahPelgniS
tloV042
)eriw4(
spma0001
esahPeerhT
tloV042
spma027
esahPeerhT
tloV084
spma063
Figure 17. AC Voltmeter
Gauge
(Volt reading on W-U Lug)
Figure 16. AC Voltmeter
Change-Over Switch
A
0
40
60
75
20
Figure 19. AC Ammeter
(Amp reading on U lug)
Figure 18. AC Ammeter
Change-Over Switch