Multiquip DCA-300SSK Portable Generator User Manual


 
PAGE 26 — DCA-300SSK SERIES — PARTS AND OPERATION MANUAL (STD) — REV. #4 (03/27/06)
Figure 12. Connecting Loads
Connecting Loads
Loads can be connected to the generator by the UVWO terminal
lugs or the convenience receptacles. (See Figure 12). Make
sure to read the operation manual before attempting to connect
a load to the generator.
To protect the UVWO output terminals from overload, a 3-
pole, 800 amp,
main
circuit breaker is provided. Make sure
to switch
ALL
circuit breakers to the "OFF" position prior to
starting the engine.
DCA-300SSK SERIES — OUTPUT TERMINAL PANEL FAMILIARIZATION
Over Current Relay
An
over current relay
(Figure 13) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the
reset button
on the over cur-
rent relay must be pressed. The over current relay is lo-
cated in the control box.
Figure 13. Over Current Relay
Maximum Power Output (KW)
The entire load connected to the UVWO output terminal lugs,
duplex and auxiliary receptacles must not exceed 264 kw in
standby or 240 kw in prime output.