Mitsubishi Electronics FX2N-5A Insect Control Equipment User Manual


 
FX2N-5A Special function block Specifications 6
6-3
Table 6.4: Voltage/current input specifications
Item Voltage input Current input
Analog input range
-10 to +10 V DC
(input resistance: 200 k
)
Adjustment is enabled with the
following conditions:
Offset value: -32000 to +5000 mV
Gain value: -5000 to +32000 mV
"Gain - Offset":
>
1000 mV
-100 to +100mV DC
(input resistance: 200k
)
Adjustment is enabled with the
following conditions:
Offset value: -320000 to +50000
µ
V
Gain value: -50000 to +320000
µ
V
"Gain - Offset":
>
10000
µ
V
(Resolution is constant.)
Change is disabled while the Voltmeter
display mode is used.
Maximum absolute input: ±15 V
-20 to +20 mA DC, +4 to +20 mA DC
(input resistance: 250
)
Adjustment is enabled with the
following conditions:
Offset value: -32000 to +10000
µ
A
Gain value: -10000 to +32000
µ
A
"Gain - Offset":
>
1000
µ
A
(Resolution is constant.)
Change is disabled while the
Amperemeter display mode is used.
Maximum absolute input: ±30 mA
Digital output
Signed 16-bit binary
(-10 to +10V at input)
Signed 12-bit binary
(-100 to +100mV at input)
Signed 15-bit binary