A-5
INSTALLATION
POWER-ARC 4000
A-5
ELECTRICAL OUTPUT
CONNECTIONS
See Figure A.1 for the location of the current control
dial, weld output terminals, ground stud, circuit
breakers, 240 and 120 volt receptacles.
WELDING CABLE CONNECTIONS
Cable Size and Length
Be sure to use welding cables that are large enough.
The correct size and length becomes especially
important when you are welding at a distance from
the welder.
Table A.1 lists recommended cable sizes and lengths
for rated current and duty cycle. Length refers to the
distance from the welder to the work and back to the
welder. Cable diameters are increased for long cable
lengths to reduce voltage drops.
TABLE A.1
RECOMMENDED WELDING CABLE
SIZE AND LENGTH
TOTAL COMBINED LENGTH OF ELECTRODE AND
WORK CABLES
Cable Size for
125 amp/
Cable Length 30% Duty Cycle
0-50 feet (0-15 meters) 6 AWG
50-100 feet (15-39 meters) 4 AWG
100-150 feet (30-46 meters) 3 AWG
150-200 feet (46061 meters) 2 AWG
200-250 feet (61-76 meters) 1 AWG
POWER ARC
4000
ELECTRODE SELECTION GUIDE
80
90
100
70
AMPS
AMPS
AMPS
AMPS
WARNING
AMPS
125
GENERATOR
6
5
4
3
2
1
FIGURE A.1 - POWER-ARC 4000 OUTPUT CONNECTIONS
1. CURRENT CONTROL DIAL
2. WELD OUTPUT TERMINALS (2)
3. GROUND STUD
4. CIRCUIT BREAKERS (2) - 20 AMP
5. RECEPTACLE - 240 VOLT, 20 AMP
6. DUPLEX RECEPTACLE - 120 VOLT, 20
AMP