WHAT SIZE FIELD WIRING CONDUIT SHOULD I USE?
Locate the size conduit across the top and the wire size along the side.
Where the two intersect on the table tells you approximately how many
wires will fill the conduit. Example: 49 wires of 18 AWG will fit in 1
1
/2"
conduit.
3. Clearing Controllers Memory / Resetting Controller
If you feel that you have misprogrammed the controller, there is a
process that will reset the memory to factory defaults and erase all
programs and data that have been entered into the controller.
1. Hold down the button, the button, and the button
simultaneously.
2. While holding down the three buttons, press and release the reset
button on the back of the front panel, then release the three
buttons.
Hold all buttons and reset until display flashes 12:00. All the memory
has been cleared and the controller may be reprogrammed.
4. Hunter Quick Check
Irrigation professionals are continuously looking for ways to more
efficiently and effectively diagnose programs in the field. Instead of
having to physically check each field wiring circuit for potential
problems, the user can run the Hunter Quick Check circuit test
procedure. This circuit diagnostic procedure is very beneficial because
NOTE: The Master Valve/Pump Start circuit will operate
during the first 20 seconds of any programmed delay to
aid in the closing of the valve and to avoid unnecessary
cycling of the pump. It is recommended that a pressure
relief valve be installed on the system should this 20
second delay be too long for a particular system.
Consult your pump contractor or supplier for details.
CONDUIT SIZES
Wire Size 1"(25 mm) 1
1
/4" (32 mm) 1
1
/2" (40mm)
18 AWG 20 34 49
16 AWG 16 30 42
14 AWG 10 18 25
12 AWG 71520
of its ability to aid in quickly identifying shorts commonly caused by
faulty solenoids or when a bare common wire touches a bare station
control wire.
To initiate the Hunter Quick Check test procedure; Press the , ,
, buttons. In the standby mode, the LCD will display all
segments (helpful when troubleshooting display problems). Press the
button to begin the Quick Check test procedure. Within seconds, the
system searches all stations in an effort to detect a high current path
through the station terminals. When a field wiring short is detected, an
ERR symbol preceded by the station number will momentarily flash on
the controller LCD display. After the
Hunter Quick Check completes
running this circuit diagnostic
procedure, the controller returns to
the automatic watering mode.
5. Test Program
The ICC allows the user a simplified method for running a test program. This
feature operates each station in numerical sequence, from the lowest to the
highest. You can start with any station. This is a great feature to check the
operation of your irrigation system.
To initiate the test program:
1. Press and hold the button. The station number will be flashing.
2. Press the or button to scroll to the station you would like the
test program to start with. Use the or button to set the run
time up to 15 minutes. The run time needs to be entered only once.
3. After a 2 second pause, the test program will begin.
DELAY