Hearth and Home Technologies BODBAY Patio Heater User Manual


 
BODEGA BAY WOOD INSERT
Page 10
August 20, 2008
R
435-1320B
FACTORY BUILT ZERO CLEARANCE FIREPLACE
(USA INSTALLATONS ONLY)
Listed Liner
Mantel
SEAL DAMPER AREA OR FACE SEAL
Figure 10A - Installation Into A Factory-Built
Zero Clearance Fireplace
The following modications of factory built replaces are
permissible: 1) removal of damper; 2) removal of smoke
shelf or bafe; 3) removal of ember catches; 4) removal
of re grate; 5) removal of viewing screen/curtain; and, 6)
removal of doors.
NOTE: Installation into replaces without a permit
will void the listing.
The factory built chimney must be listed per UL 127 and
meet the type HT requirements of UL 103. Factory built
replace chimneys tested to UL 127-1998, may be at the
replace manufacturer’s option, tested to the same criteria
as UL 103 HT requirements. If the chimney is not listed
as meeting HT requirements, or if the factory built re-
place was tested prior to 1998, a full height listed chimney
liner must be installed from the appliance ue collar to the
chimney top. The liner must meet type HT requirements
(2100ºF) per UL 1777.
The liner must be securely attached to the insert ue collar
and the chimney top. To prevent room air passage to the
chimney cavity of the replace, seal either the damper area
around the chimney liner with high temperature sealant or
the replace front with berglass batting.
The replace must not be altered, except that the damper
may be removed to accommodate a direct-connect starter
pipe or chimney liner, and external trim pieces which do
not affect the operation of the replace may be removed
providing they can be stored on or within the replace for
reassembly if the insert is removed.
The Quadra-Fire Bodega Bay ACT Wood Stove Insert is
listed to UL 1482 Standard and approved for installation into
listed factory built zero clearance replaces listed to UL 127
conforming to the following specications and instructions:
Minimum Width of cavity opening:
30 in.
Minimum Height:
21 in.
Minimum Depth from front to rear:
16-1/4 in.
The original factory-built clearance replace chimney cap
must be re-installed after installing the approved chim-
ney liner meeting type H.T. requirements (2100°F) per UL
1777. The air ow of the factory-built zero-clearance re-
place system must not be altered. The ue liner top support
attachment must not reduce the air ow for the existing air-
cooled chimney system.
NOTE: Refer to chimney liner manufacturer for rec-
ommendations on supporting the liner.
The permanent metal warning label provided must be
attached to the back of the replace, with screws or nails,
stating that the replace may have been altered to accom-
modate the insert, and must be returned to original condition
for use as a conventional replace.
If the hearth extension is lower than the replace opening,
the portion of the insert extending onto the hearth must be
supported. Manufacturer designed adjustable support kit
can be ordered from your dealer. (See page 14).
Final approval of this installation type is contingent upon
the authority having jurisdiction.
Fire Risk.
When lining air-cooled factory-built chimneys:.
Run chimney liner approved to UL 1777 Type
HT requirements (2100 degrees F)
Re-install original factory built chimney cap
ONLY
DO NOT block cooling air openings in chimney
Blocking cooling air will overheat the chimney
WARNING