6.5.2 PARTS NOT INCLUDED IN FUEL SYSTEM
The propane fuel system does NOT include such
items as (a) gas tank, (b) gas piping, (c) fittings, (d)
valves, and (e) primary regulator, used to store the
gaseous fuel and deliver it to the gaseous fuel sole-
noid (Figure 6.11).
Use only approved components in the fuel sup-
ply system. All components must be properly
installed in accordance with applicable codes.
Improper installation or use of unauthorized
components may result in fire or an explosion.
Follow approved methods to test the system
for leaks. No leakage is permitted. Do not allow
fuel vapors to enter the vehicle interior.
Figure 6.11 – Typical Propane Gas Fuel System
6.5.3 SOME IMPORTANT CONSIDERATIONS
When installing an LP gas system, consider seriously
the following items:
• All fittings, lines, hoses and clamps must be tight
and free of leaks. Apply a pipe sealant to threads
when assembling threaded connections. This
reduces the possibility of leakage.
• Test the entire fuel system for leaks using approved
test methods.
• Optimum gas pressure at the inlet to the gaseous
fuel solenoid valve and secondary regulator is 11
inches water column.
• The installer’s fuel supply connection point is at the
gaseous fuel solenoid valve. This is a 3/4-inch
(female) connection. Provide a suitable 3/4-inch NPT
(male) connector to attach to the fuel supply line.
• Use a length of approved flexible fuel hose between
the gaseous fuel solenoid valve and rigid gas pip-
ing. The flexible line should be at least 6 inches
longer than necessary.
6.5.4 VAPOR WITHDRAWAL
LP gas is stored in pressure tanks as a liquid. The
gas systems used with these generators were
designed only for vapor withdrawal type systems.
Vapor withdrawal systems use the gas vapors that
form above the liquid fuel in the tank. Do NOT
attempt to use the generator with any liquid with-
drawal type system.
6.5.5 PRIMARY REGULATOR
Gas pressure delivered to the solenoid valve must be
properly regulated by means of a primary gas regula-
tor. Mount the primary regulator at the gas tank out-
let or in the supply line from the gas tank. The fol-
lowing rules apply:
• For best results, the primary regulator supplies
gaseous fuel to the secondary regulator at 11 inch-
es water column. Do NOT exceed 14 inches water
column.
• The installer must be sure the primary regulator is
rated at sufficient gas flow to operate the generator
plus all other gas appliances in the circuit.
NOTE:
Recommended MINIMUM gas flow rate for all air-
cooled PRIMEPACT series generators is 67 cubic
feet per hour.
If an existing primary gas regulator does not have
a sufficient flow capacity for the generator and
other gas appliances in the circuit, (a) install a pri-
mary regulator with adequate flow rate, or (b)
install a separate regulator only and rated at least
67 cubic feet per hour. The inlet side of any pri-
mary regulator that supplies the generator must
connect directly to a gas pressure tank. Do NOT
tee the generator line into a gas circuit feeding
other areas.
6.5.6 GASEOUS CARBURETION
LP gas vapors should be supplied to the secondary
regulator inlet at about 11 inches water column (pos-
itive pressure). The engine pistons draw air in during
the intake stroke (Figure 6.12). This air passes
through a carburetor venturi, which creates a low
pressure that is proportional to the quantity of air
being pumped. The low pressure from the carburetor
venturi acts on the regulator diaphragm to pull the
diaphragm toward the source of low pressure. A lever
attached to the diaphragm opens a valve to permit
gas glow through the carburetor.
◆
◆
◆
◆