Generac Portable Products Power Transfer System
5
6. From the load management plan, determine the
load that is to be connected to Load Manager
switch circuit A. Turn that load center circuit
breaker to its OFF position. Loosen the screw
that retains the wire to this breaker, then detach
the wire. Figure 5 shows the selected load wire
detached from the circuit breaker.
7. Find the black and red wires marked A that come
from the Load Manager switch. Using good
workmanship, route both of these wires near the
selected circuit breaker. Trim and strip the red A
wire and install it properly into the circuit breaker.
8. Trim and strip the black A wire to mate with the
wire previously detached from the breaker. Secure
the wire ends with a wire nut. Neatly dress the
wires into the load center, as shown in Figure 6.
IMPORTANT:The installer should never cross the
black and red leads from the Load Manager switch.
Doing so will void the warranty and could cause
significant damage to Load Manager components
and the generator.
Make Sure:
The RED wire from the Load Manager switch is
always connected to the circuit breaker.
The BLACK wire from the Load Manager switch is
always connected to the wire going to the load.
DANGER! You must connect the Load
Manager switch wires as described or serious
damage to the equipment or yourself may result.
9. Select the load center circuit that will become load
management circuit B. Repeat Steps 6 through 8
for the red and black wires marked B coming
from the Load Manager switch.
10. If you wish to connect a 240 Volt AC two-pole
circuit, such as a well pump, proceed as follows:
a. Turn off the two-pole circuit breaker used for
the pump circuit and detach the load wires
from that breaker.
b. Select the four wires marked C and D
coming from the Load Manager switch
conduit and route them close to the selected
circuit breaker(s).
c. Repeat Steps 6 through 8 for each pair of red
and black wires C and D.
d. A typical two-pole circuit connection is shown
in simplified form in Figure 7.
Figure 7 Two-pole Connection
Figure 5 Wire Detached From Breaker
Wire removed
Figure 6 Single-pole Connection